2G40UM产品概述
UL® listed to UL508 and CSA certified to C22.2 No. 14 V-EA manual motor controllers are horsepower rated for AC across-the-line motor starting, suitable for motor disconnect means and overload protection. They also can be used for AC general use, AC resistance, AC discharge lamps and AC incandescent lamps. Altech/ABL SURSUM V-EA miniature DIN rail mount circuit breakers provide an opportunity for major cost and installation time savings and superior circuit protection. Six trip characteristics are UL® listed. All trip characteristics are internationally defined and accepted. The “G” characteristic matches USA and Canadian thermal/magnetic trip norms. All rated currents have the same housing dimensions and terminal sizes. The V-EA can be loaded with full rated current (100% breaker). Recognized with Line/Load reversibility, i.e., power feed can be field or factory wired to the screw-cage clamp terminals at the “top,” range 18 AWG to 3 AWG, or at the “bottom,” range 18 AWG to 2 AWG. The V-EA/U is intended for OEM industrial applications.
Technical Specifications
Voltage Rating: 480Y/277 VAC (480 VAC phase-to-phase, 277 VAC phase-to-ground/neutral).
Interrupting Capacity: 10 kA with UL® listed RK5 back-up fuse or MCCB.
Electrical/Mechanical Endurance: 10,000 ON/OFF operations.
Calibration Temperature: 40°C (104°F).
Terminal Tightening Torque: 20 in.-lb.
International Approvals: For various trip characteristics and rated currents, Germanischer Lloyd, SEV, SEMKO, NEMKO, etc. VDE approved on up to 25 A on B, C, and D-trip. CE mark is standard.
Z-Characteristic — Thermal one-hour trip zone 1.05 to 1.35 times rated current (RC): Magnetic 100 ms trip boundary 2 to 3 times RC.
UL508 Listed V-EA Miniature Circuit Breakers/Manual Motor Controllers
Rated Current: 3 A 480 Y/277 VAC, 50/60 Hz
10 kA Short Circuit
DIN Rail Mount
17.5 mm Width per Pole
Thermal Magnetic