The PCP2 Series is designed to protect against phase reversal only on any 208-480 V three-phase system. The relay is energized and the LED is on when the A-B-C sequence is correct. Any incorrect sequence will either de-energize the relay and turn off the LED or prevent the relay from energizing.
Features:
Universal Voltage: One Unit Works on any 208-480 V System (PCP2)
Adjustable Undervoltage Setting of 75-95% Nominal Voltage (PAP)
Standard 8-Pin Octal Socket Mounting
LED Indicates Both Normal and Fault Conditions
Compatible with Both Wye and Delta Systems
Automatic Reset
PCP2 Protects Against:
Phase Reversal Only
Specifications:
SPDT 10 A @ 240 VAC/30 VDC
PCP2 Dimensions: 1.7" × 2.4" × 3.1"
PAP Dimensions: 1.7" × 2.4" × 3.5"
Temperature: –28° to +65°C