VAKPU产品概述
Voltage Monitor Relays provide protection to equipment where an over or under voltage condition is potentially damaging. VAKP Series (Over/Under): Pick-up voltage setting is adjustable from 85-115% of nominal. Drop-out voltage is adjustable from 75-95% of pick-up setting. When the monitored voltage exceeds the pick-up setting, the relay is energized. When the voltage is below the drop-out setting for a period longer than the adjustable time delay of 0.5-10 seconds, the relay de-energizes. VWKP Series (Band): Over voltage setting from 100-125% of nominal. Under voltage setting from 75-100%. The relay energizes when the monitored voltage is between the over and under voltage settings. The relay de-energizes when the voltage falls outside the over and under voltage settings for a period longer than the adjustable time delay of 0.5-10 seconds.
Features:
Monitors AC Single-Phase or DC Voltages
Standard 8-Pin Octal Socket Mounting
LED Indicates Relay Status
Adjustable 0.5-10 Seconds Time Delay on Drop-Out
Specifications:
DPDT 10 A @ 240 VAC/30 VDC
Dimensions: 1.7" × 2.4" × 3.5"
Temperature: –28° to +55°C