HDM3M150L产品概述
Breaker Mounted Immediately Ahead of Motor Starter
Siemens motor circuit protectors are recommended for use in combination motor starters to provide selective short-circuit protection for the motor branch circuit. The adjustable instantaneous trip feature of the Siemens motor circuit protector provides for a trip setting slightly above the peak motor in-rush current. With this setting, no delay is introduced in opening the circuit when a fault occurs. This circuit breaker has no time-delay trip element. Therefore it must be used in conjunction with, and immediately ahead of, the motor running overcurrent protection device.
3-Phase induction type motors (Siemens motor circuit protectors for branch circuit use with alternating-current combination, full voltage motor starters.)