HNF361R产品概述
Standards
UL98 Approved Per File #4776
Suitable for Use as Service Entrance Equipment (Where Applicable)
Meets NEMA Standard KS-1-1990 for Type HD Switches
Seismic Qualification — All Switches Have Been Tested and Comply with the 2007 California Building Code CBC (Zone 4)
Fusible Switches (and Non-Fusible Switches When Protected by Fuses)
30-600 A — 10,000 AIC with Class H Fuses
30-600 — 200,000 with Class R, J or T Fuses
800 and 1200 A — 200,000 AIC with Class L or T Fuse
600 VAC Fusible and Non-Fusible with Viewing Window
Rugged Installer-Friendly Enclosure Design Features a Gasket Flange with Continuously Welded Seams (NEMA 12 and 4X)
Tool-Free Cover Latches (NEMA 12 and 4X)
Two, Three and Four Point Mounting
Metal Handle with Large Insulating Grip Features a Positive Stop in Both ON and OFF Position
Ground Lugs Provided as Standard (NEMA 12 and 4X)
Type 12 Enclosures are Fabricated from Galvanized Steel and Are Also Rated for 3R/3S Outdoor Applications
Type 4X Stainless Steel Switches (30-200 A) Are Provided with Stainless Steel Interior Parts
The Widest Range of Accessories Available Including 200% Neutrals, Gold-Plated PLC Auxiliary Contacts and Isolated Ground Kits