SUINT1500RTXL2UA产品概述
True online, double conversion UPS provides pure sine wave AC output at all times
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time to battery
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
Accepts input voltages between 130 and 275V (between 160 and 275V at loads over 70%), regulating output to 200/208/220/230/240V +/-2%
1500VA
1200 watt power capacity with
IEC-320-C13 output receptacles
IEC320-C14 input connection accepts
variety of detachable cordsets to match country or site-specific wall receptacles
2 C13 to C14 output power cables included
Standard internal battery set provides 12 minutes runtime at half load and 4.5 minutes runtime at full load
Optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack compatible) and BP48V27-2US (multi-pack compatible) external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Highly efficient operation in optional Economy Mode setting, saving BTU heat output and energy costs.
Innovative design makes unit adaptable to rackmount, tower, or stacking applications
Uses only
rack spaces (2U) in standard 19-inch rack
Optional 2-9USTAND kit enables upright tower placement
Optional 2POSTRMKITWM enables 2-post rackmount or wallmount installation
Supports simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS
? Slot for optional SNMP/web card (Part Number: SNMPWEBCARD)
PowerAlert unattended shutdown software and communications cabling included
Compatible with Tripp Lite's WatchDog software
Fault tolerant electronic bypass maintains utility output during
variety of UPS fault conditions
Optional PDUBHV10 bypass PDU enables hot-swappable UPS replacement with no disruption to connected equipment
Built-in Emergency Power Off (EPO) interface with cable
Single-line tel/DSL or Ethernet network surge suppression
Integrated 2-bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has
outlets)